10 • 400 Hot Springs Road, Carson City NV 89706 • (775) 883-0820 • Fax (775) 883-0827 • www.hytek.com
HY5600B
TEC Controller Evaluation Board
Figure 1
Procedure for Setting Up the
HY5600 Evaluation Board
1. Connect a Thermoelectric Cooler and a
Thermistor to the evaluation board as shown in
the schematic diagram. A phone jack along
with interconnect cables are provided for
interfacing the Evaluation Board to the Ther-
moelectric Cooler and Thermistor.
2. Select a Temperature set resistor (R
S
) that will
program the HY5600 to regulate the TEC to
the desired temperature. For example: A
56K
Ω
resistor will set the TEC to a tempera-
ture of –10°C if Dale 1M1002, 10K
Ω
thermistor
is used. See the "Set Temperature vs. Pro-
gram Resistor (R
S
)" curve in HY5600 Data
Sheet to determine the correct value of R
S
for
your application.
Caution: The HY5600
controller will supply maximum programmed
cooling current to the TEC if R
S
is not present.
The thermoelectric cooler could be damaged if
this condition exists for a prolonged period of
time.
3. A 1 µF capacitor and a 6.8M
Ω
resistor have
been selected for the loop stabilization
components C
L
and R
L
. These values will
more than likely be satisfactory for most
applications. They can easily be changed if
they are not. (Reference the HY5600 Data
Sheet.)
4. There is a position for R
G
, the loop gain
control resistor, on the evaluation board.
However, this resistor has been omitted. This
is because there is 10M
Ω
resistor internal to
the HY5600 that is in parallel with R
G
that
will, in most cases, provide sufficient loop
gain.
Thermoelectric Cooler Controller Evaluation Board
TEC
Controllers
Laser
D
iode
Drivers
Micro-heaters
The HY5600 Evaluation Board
is a printed
circuit board containing the HY5600 TEC Controller
plus other components required to make an evalua-
tion temperature controller for Thermoelectric Cool-
ers. This evaluation board provides the means to
quickly interface the HY5600 with a Thermoelectric
Cooler and to evaluate performance before designing
a printed circuit board. A schematic diagram for the
test board is shown. The evaluation board contains
loop compensation components of 1µF and 6.8 M
Ω
(C
L
and R
L
). These components can easily be re-
placed if it is found that other values are more suit-
able. Terminals for the temperature set resistor (R
S
)
are provided on the Evaluation Board for the user to
set the desired TEC temperature.
400 Hot Springs Road, Carson City NV 89706 • (775) 883-0820 • Fax (775) 883-0827 • www.hytek.com • 11
HY5600B
TEC Controller Evaluation Board
5. Connect the V
S
and V
DD
power supplies to the test
board. The desired values for these supplies should be
set before the power supplies are connected to the
evaluation board. Note that V
S
should be able to supply
more than 2 Amperes of current. Before turning off the
power supplies, make certain the TEC, the Thermistor
and the temperature set resistor (R
S
) are connected to
the Evaluation Board. In addition, SW1 should be in the
“off” position.
6. Turn on the power supplies. Maximum current will flow
through the TEC as long as the temperature set resistor
R
S
is greater than the resistance of the Thermistor. The
HY5600 will continue to supply maximum cooling current
until the resistance of the Thermistor increases to a value
equal the R
S
. The current supplied by the HY5600 will
Procedure for Setting Up the HY5600 Evaluation Board
(continued)
then decrease to a value required to maintain the TEC at
the set temperature.
7. Potentiometer R
C
controls the maximum current that the
HY5600 can supply to the TEC. The Evaluation Board
has been adjusted at the factory so that a maximum of
0.8 Amperes flows through the Thermoelectric Cooler. If a
higher or lower value of cooling current is desired, push
Switch #1 to the “on” position. This action will force the
HY5600 to supply maximum cooling current to the TEC.
This maximum cooling current can be adjusted to the
desired value with the potentiometer labeled R
C
. Do not
exceed the maximum current specification for the TEC.
Return SW1 to the “off” position for normal operation.
Figure 2
12 • 400 Hot Springs Road, Carson City NV 89706 • (775) 883-0820 • Fax (775) 883-0827 • www.hytek.com
HY5600B
TEC Controller Evaluation Board
The output of the temperature measuring circuit of the
HY5600 is Pin 4. Test Point 4 on the evaluation board corre-
sponds to this output. The temperature measurement circuit
of the HY5600 is illustrated in Figure 3 where R
T
is the ther-
mistor that measures the temperature of the Thermoelectric
Cooler and R
S
is the temperature set resistor. The output
voltage (E
O
) at Test Point 4 is given by the equation below.
This output feeds the integrator portion of the HY5600 which
in turn applies power to the TEC. Cooling of the TEC results
The temperature controlling stability of the HY5600 vs. Ther-
moelectric Cooler (TEC) drive current is measured using the
test setup illustrated in Figure 4. The thermoelectric cooler
and temperature sensing thermistor are placed in a tem-
perature chamber. An identical thermistor is mounted in inti-
mate contact with the sensing thermistor. Both thermistors
are embedded in an aluminum block that is attached to the
top surface of the TEC. The bottom face of the TEC is at-
tached to a heat sink. The temperature of the controlling
Measuring the Temperature Regulating Performance of the HY5600
until R
T
equals R
S
. This produces a voltage (E
O
) of 2.500
Volts between TP 4 and signal ground. The Voltage/Tem-
perature coefficient at TP 4 is approximately 50 mVolts per
°C when this occurs. Monitoring Test Point 4 will tell the
user when the loop is stabilized and how accurately the
temperature is controlled. When the loop has stabilized, the
voltage at TP 4 will be stable to better than 1 mVolt. This
equates to a temperature stability of better than .02 °C.
Figure 3
thermistor is set to approximately 25°C by selecting an R
S
value of 10K
Ω
. R
S
is a precision temperature stable resistor.
TEC drive current is monitored as the Temperature of the
chamber is increased above 25°C. Resistance of the sec-
ond thermistor is recorded and converted to temperature for
various TEC drive currents. A typical plot of Temperature
stability vs. TEC Drive Current is shown in Figure 6.
Figure 4
400 Hot Springs Road, Carson City NV 89706 • (775) 883-0820 • Fax (775) 883-0827 • www.hytek.com • 13
The temperature controlling stability of the HY5600 vs. Base
Temperature* is measured using the test setup illustrated in
Figure 5. The HY5600 is placed inside the temperature
chamber. The thermoelectric cooler / thermistor assembly
is placed outside the chamber. In addition, the 13K
Ω
tem-
perature set resistor R
S
is located outside the chamber to
eliminate any temperature effects due to this resistor. This
* Base Temperature is the temperature of the aluminum
heat spreader (Base) of the HY5600. In the experiment il-
lustrated in Figure 5, the programmed temperature to the
TEC assembly and its ambient temperature are almost
equal. The TEC current is therefore almost zero amperes
thus eliminating any self heating effects in the HY5600. In
HY5600B
TEC Controller Evaluation Board
value of R
S
sets the temperature of the controlling ther-
mistor to approximately 18°C. The temperature of the test
chamber is varied from –55°C to +110°C. Resistance of the
temperature measuring thermistor is recorded and con-
verted to temperature. A typical plot of Temperature stability
vs. Base temperature of the HY5600 is shown in Figure 7.
this case, the temperature of the HY5600 is virtually equal
to the temperature of the chamber. In practice, the tem-
perature of the base of the HY5600 is a function of the TEC
drive current, the HY5600 heat sink size, the air flow
across the heat sink and the temperature of the surround-
ing air.
Figure 5
Figure 6
Figure 7